After a successful initial verification test on a repaired R-123 chiller that was not evacuated, how soon…
Leak repair requirements · EPA 608 Type III. The correct answer, and the reasoning behind it.
Allowable annual leak rates for low-pressure appliances.
The question
After a successful initial verification test on a repaired R-123 chiller that was not evacuated, how soon must the follow-up verification test be done?
- Within 30 days
- Within 10 daysCorrect answer
- Within 24 hours
- Within 12 months
Why “Within 10 days” is correct
40 CFR 82.157(e)(2) requires a follow-up verification test within 10 days of the successful initial test. If the appliance was evacuated for the repair, the 10 days run from when it reaches normal operating conditions.
Source: 40 CFR 82.157(e)
Why the other answers are wrong
- Within 30 days — 30 days is the repair deadline, not the follow-up test window.
- Within 24 hours — The rule allows 10 days, not one day.
- Within 12 months — 12 months relates to presuming leaks repaired, not to follow-up testing.
Practice more of this
More EPA 608 Type III practice questions, or see every EPA 608 practice test.