Under 40 CFR Part 82, what is its leak rate?

Leak repair requirements · EPA 608 Type III. The correct answer, and the reasoning behind it.

Allowable annual leak rates for low-pressure appliances.

The question

An owner runs a 400-pound R-123 system in a cold-storage warehouse for perishable food. Under 40 CFR Part 82, what is its leak rate?

  • 10 percent
  • 30 percent
  • 15 percent
  • 20 percentCorrect answer

Why “20 percent” is correct

EPA classes cold-storage warehouse equipment as commercial refrigeration. Commercial refrigeration appliances with 50 pounds or more of an ozone-depleting refrigerant have a 20 percent leak rate.

Source: 40 CFR 82.157(c); EPA: Leak Repair Requirements

Why the other answers are wrong

  • 10 percent — 10 percent applies to comfort cooling and other appliances.
  • 30 percent — 30 percent is for industrial process refrigeration.
  • 15 percent — 15 percent is not a leak rate in Part 82.

Practice more of this

More EPA 608 Type III practice questions, or see every EPA 608 practice test.

Unofficial, not affiliated with the EPA or any EPA-approved certifying organization. Questions are original practice written from public EPA material, not real exam questions.