Which method, used by itself, does not meet EPA's definition of a leak inspection on an R-11 chiller?
Leak detection · EPA 608 Type III. The correct answer, and the reasoning behind it.
Pressurizing low-pressure systems for leak tests, signs of leaks, inspections and reports.
The question
Which method, used by itself, does not meet EPA's definition of a leak inspection on an R-11 chiller?
- An electronic leak detector
- A standing vacuum decay testCorrect answer
- A bubble test at the joints
- An ultrasonic leak test
Why “A standing vacuum decay test” is correct
A leak inspection must find where the leaks are. Methods that only show that the appliance is leaking, such as standing pressure or vacuum decay tests, must be paired with a method that locates the leak, like an electronic detector, bubble test or ultrasonic test.
Source: 40 CFR 82.152
Why the other answers are wrong
- An electronic leak detector — A properly maintained detector can locate leaks, so it qualifies.
- A bubble test at the joints — Bubble tests locate leaks and are listed as a potential method.
- An ultrasonic leak test — Ultrasonic testing is named in the definition as a method that can locate leaks.
Practice more of this
More EPA 608 Type III practice questions, or see every EPA 608 practice test.