What must a technician do after recovering refrigerant from an R-123 chiller and before opening it for a major repair?

Recovery requirements · EPA 608 Type III. The correct answer, and the reasoning behind it.

Evacuation levels for low-pressure appliances, and major versus non-major repairs.

The question

What must a technician do after recovering refrigerant from an R-123 chiller and before opening it for a major repair?

  • Get written permission from the building owner
  • Send a sample of the recovered refrigerant to a lab for analysis
  • Verify the required evacuation level has been reachedCorrect answer
  • Notify EPA within 30 days of the repair

Why “Verify the required evacuation level has been reached” is correct

40 CFR 82.156(a) says a technician must verify that the applicable level of evacuation has been reached in the appliance, or in the part being serviced, before it is opened. Recovering to a reading once is not enough if the pressure has not been confirmed.

Source: 40 CFR 82.156(a)

Why the other answers are wrong

  • Get written permission from the building owner — Owner permission is not what 40 CFR 82.156(a) requires before opening.
  • Send a sample of the recovered refrigerant to a lab for analysis — Lab analysis is part of reclamation, not a step before opening the appliance.
  • Notify EPA within 30 days of the repair — There is no EPA notice required before opening an appliance for repair.