If this is not a major repair, what is the highest pressure the chiller or isolated section may be at when…
Recovery requirements · EPA 608 Type III. The correct answer, and the reasoning behind it.
Evacuation levels for low-pressure appliances, and major versus non-major repairs.
The question
Before servicing a low-pressure chiller, a technician wants to drain the oil only. If this is not a major repair, what is the highest pressure the chiller or isolated section may be at when it is opened for the oil change?
- 0 psig
- 10 psig
- 5 psigCorrect answer
- 15 psig
Why “5 psig” is correct
For oil changes, 40 CFR 82.156(a)(1)(iii) allows the appliance to be evacuated or pressurized to no higher than 5 psig before opening, or the oil can be drained into a receiver that is brought to 5 psig or less. EPA notes that changing oil above 5 psig is a violation because oil holds a lot of dissolved refrigerant.
Source: 40 CFR 82.156(a)(1)(iii); EPA: Service Practice Requirements
Why the other answers are wrong
- 0 psig — 0 psig is the general non-major limit; oil changes have their own, slightly higher 5 psig limit.
- 10 psig — 10 psig is above the oil-change limit.
- 15 psig — 15 psig is well above the limit and close to a typical rupture disc setting.