A refrigerant has a liquid-phase saturation pressure of 200 psia at 104 °F. How does 40 CFR 82.152 classify…

Refrigeration · EPA 608 Type II. The correct answer, and the reasoning behind it.

Identifying refrigerants, system components and the state of refrigerant in each.

The question

A refrigerant has a liquid-phase saturation pressure of 200 psia at 104 °F. How does 40 CFR 82.152 classify an appliance that uses it?

  • Low-pressure
  • Medium-pressure
  • Very high-pressure
  • High-pressureCorrect answer

Why “High-pressure” is correct

A high-pressure appliance uses a refrigerant with a saturation pressure between 170 and 355 psia at 104 °F. 200 psia falls in that range, alongside refrigerants such as R-22 and R-410A.

Source: 40 CFR 82.152

Why the other answers are wrong

  • Low-pressure — Low-pressure means below 45 psia at 104 °F.
  • Medium-pressure — Medium-pressure covers 45 to 170 psia at 104 °F.
  • Very high-pressure — Very high-pressure means above 355 psia, or a critical temperature below 104 °F.