Which requirement applies to a retrofit or retirement plan for a leaking 300-pound R-22 commercial refrigeration system?
Leak repair requirements · EPA 608 Type II. The correct answer, and the reasoning behind it.
Leak-rate thresholds, repair deadlines, extensions and records.
The question
Which requirement applies to a retrofit or retirement plan for a leaking 300-pound R-22 commercial refrigeration system?
- It must be signed by the technician who first found the leak
- It must be mailed to EPA within 10 days
- It must be filed with the state fire marshal
- It must be signed by a company official and kept on siteCorrect answer
Why “It must be signed by a company official and kept on site” is correct
The plan must be signed by an authorized company official, dated, kept at the appliance site in paper or electronic form, and available to EPA on request. It is not routinely sent to EPA.
Source: 40 CFR 82.157(h)(3); EPA: Leak Repair Requirements
Why the other answers are wrong
- It must be signed by the technician who first found the leak — The rule calls for an authorized company official, not the technician.
- It must be mailed to EPA within 10 days — The plan is kept on site and shown to EPA on request, not mailed within 10 days.
- It must be filed with the state fire marshal — No filing with a fire marshal is required by this rule.
Practice more of this
More EPA 608 Type II practice questions, or see every EPA 608 practice test.