Using post-1993 recovery equipment, to what level must the isolated section be evacuated?
Recovery requirements · EPA 608 Type II. The correct answer, and the reasoning behind it.
Evacuation levels by charge size and equipment date, major repairs, and system-dependent limits.
The question
A large R-22 system holds 500 pounds in total. The technician isolates a section holding 150 pounds and will open only that section. Using post-1993 recovery equipment, to what level must the isolated section be evacuated?
- 10 inches of Hg vacuum
- 4 inches of Hg vacuum
- 15 inches of Hg vacuum
- 0 inches of Hg vacuumCorrect answer
Why “0 inches of Hg vacuum” is correct
Table 1 rows apply to a high-pressure appliance or an isolated component of one, based on that component's full charge. A high-pressure isolated component holding less than 200 pounds must be evacuated to 0 inches of Hg vacuum.
Source: 40 CFR 82.156(a), Table 1; 40 CFR 82.156(a)
Why the other answers are wrong
- 10 inches of Hg vacuum — 10 inches would apply if the isolated component itself held 200 pounds or more.
- 4 inches of Hg vacuum — 4 inches is a pre-1993 level and does not apply to a high-pressure component under 200 pounds.
- 15 inches of Hg vacuum — 15 inches is a medium-pressure level; R-22 is high-pressure.
Practice more of this
More EPA 608 Type II practice questions, or see every EPA 608 practice test.
Unofficial, not affiliated with the EPA or any EPA-approved certifying organization. Questions are original practice written from public EPA material, not real exam questions.