Using recovery equipment manufactured in 2015, what evacuation level is required before a major repair?

Recovery requirements · EPA 608 Type II. The correct answer, and the reasoning behind it.

Evacuation levels by charge size and equipment date, major repairs, and system-dependent limits.

The question

A process chiller holds 250 pounds of R-407C. Using recovery equipment manufactured in 2015, what evacuation level is required before a major repair?

  • 0 inches of Hg vacuum
  • 10 inches of Hg vacuumCorrect answer
  • 4 inches of Hg vacuum
  • 15 inches of Hg vacuum

Why “10 inches of Hg vacuum” is correct

R-407C is a high-pressure refrigerant. A high-pressure appliance with a full charge of 200 pounds or more must be pulled to 10 inches of Hg vacuum with equipment made on or after November 15, 1993, or 4 inches with older equipment.

Source: 40 CFR 82.156(a), Table 1; 40 CFR 82.152

Why the other answers are wrong

  • 0 inches of Hg vacuum — 0 inches applies to high-pressure appliances under 200 pounds, and this one holds 250.
  • 4 inches of Hg vacuum — 4 inches is the level for this row only with recovery equipment made before November 15, 1993.
  • 15 inches of Hg vacuum — 15 inches is for medium-pressure appliances of 200 pounds or more, and R-407C is high-pressure.