To what level must the appliance be evacuated before it is opened?
Recovery requirements · EPA 608 Type II. The correct answer, and the reasoning behind it.
Evacuation levels by charge size and equipment date, major repairs, and system-dependent limits.
The question
A technician is replacing the compressor on a very high-pressure appliance that uses R-23, using recovery equipment manufactured in 2019. To what level must the appliance be evacuated before it is opened?
- 0 inches of Hg vacuumCorrect answer
- 4 inches of Hg vacuum
- 10 inches of Hg vacuum
- 15 inches of Hg vacuum
Why “0 inches of Hg vacuum” is correct
Table 1 sets a single level for very high-pressure appliances: 0 inches of Hg vacuum, whatever the recovery equipment date or charge size. R-23 is one of the examples EPA gives of a very high-pressure refrigerant.
Source: 40 CFR 82.156(a), Table 1; 40 CFR 82.152
Why the other answers are wrong
- 4 inches of Hg vacuum — 4 inches applies to some medium- and high-pressure rows with pre-1993 equipment, not to very high-pressure appliances.
- 10 inches of Hg vacuum — 10 inches is for large high-pressure or small medium-pressure appliances with newer equipment.
- 15 inches of Hg vacuum — 15 inches is only for medium-pressure appliances of 200 pounds or more with newer equipment.