Under 40 CFR 82.164, which requirement applies to a certified refrigerant reclaimer?
The three Rs · EPA 608 Core. The correct answer, and the reasoning behind it.
What recover, recycle and reclaim each mean.
The question
Under 40 CFR 82.164, which requirement applies to a certified refrigerant reclaimer?
- It must return reclaimed refrigerant only to the original owner
- It may release up to 5 percent of refrigerant during processing
- It must test each batch against Appendix A specificationsCorrect answer
- It must hold Type III technician certification
Why “It must test each batch against Appendix A specifications” is correct
Certified reclaimers must reprocess refrigerant to the Appendix A specifications (based on AHRI 700-2016), verify each batch by the prescribed analysis, release no more than 1.5 percent during reclamation, dispose of wastes properly and keep records and annual reports.
Source: 40 CFR 82.164(a)
Why the other answers are wrong
- It must return reclaimed refrigerant only to the original owner — Reclaimed refrigerant may be sold to new owners; that is the point of reclamation.
- It may release up to 5 percent of refrigerant during processing — The limit is 1.5 percent, not 5 percent.
- It must hold Type III technician certification — Reclaimer certification is separate from technician certification.