If the refrigerant warms from 70 °F to 90 °F, what happens to its pressure?
Refrigeration · EPA 608 Type III. The correct answer, and the reasoning behind it.
Purge units and pressure-temperature behaviour of low-pressure refrigerants.
The question
A closed R-123 chiller holds both liquid and vapor. If the refrigerant warms from 70 °F to 90 °F, what happens to its pressure?
- It goes from below to above atmospheric pressureCorrect answer
- It stays the same, since the chiller is closed
- It falls further into a vacuum
- It jumps to about 100 psig
Why “It goes from below to above atmospheric pressure” is correct
R-123 boils at about 82 °F at atmospheric pressure. Below that temperature its saturation pressure is a vacuum; above it, slightly positive. The same rule is why warming the refrigerant can bring a chiller above atmosphere for leak testing.
Source: EPA: Test Topics; Hudson Technologies R-123 and R-11 P-T charts
Why the other answers are wrong
- It stays the same, since the chiller is closed — Saturated refrigerant pressure follows temperature even in a closed vessel.
- It falls further into a vacuum — Warming raises saturation pressure; it does not lower it.
- It jumps to about 100 psig — R-123 at 90 °F is only slightly above atmospheric pressure.