Under the leaky-appliance rule, what is the first thing the technician should do?
Recovery requirements · EPA 608 Type III. The correct answer, and the reasoning behind it.
Evacuation levels for low-pressure appliances, and major versus non-major repairs.
The question
An R-11 chiller has a leaking evaporator that cannot reach Table 1 levels. Under the leaky-appliance rule, what is the first thing the technician should do?
- Evacuate the whole chiller to 0 psig and open it
- Isolate leaking components from non-leaking ones where possibleCorrect answer
- Pressurize the whole chiller with nitrogen to locate the leak first
- Vent the remaining vapor because it is contaminated
Why “Isolate leaking components from non-leaking ones where possible” is correct
40 CFR 82.156(a)(2) starts by asking the technician to isolate leaking from non-leaking components wherever possible. The non-leaking parts then go to the Table 1 level and the leaking parts to the lowest level attainable without substantial contamination, never above 0 psig.
Source: 40 CFR 82.156(a)(2)
Why the other answers are wrong
- Evacuate the whole chiller to 0 psig and open it — Non-leaking parts must still reach Table 1 levels, so the whole chiller cannot simply be taken to 0 psig.
- Pressurize the whole chiller with nitrogen to locate the leak first — The rule's first step is isolating leaking components, and adding nitrogen would contaminate the refrigerant still to be recovered.
- Vent the remaining vapor because it is contaminated — Venting refrigerant is prohibited; contaminated refrigerant is still recovered.