When charging refrigerant into an evacuated low-pressure centrifugal chiller, what should go in first?

Recharging techniques · EPA 608 Type III. The correct answer, and the reasoning behind it.

Charging vapor before liquid, and charging centrifugals through the evaporator valve.

The question

When charging refrigerant into an evacuated low-pressure centrifugal chiller, what should go in first?

  • VaporCorrect answer
  • Liquid
  • Nitrogen
  • Oil

Why “Vapor” is correct

An evacuated chiller is in a deep vacuum. Charging vapor first raises the pressure safely before liquid is introduced, which protects the tubes from freezing.

Source: EPA: Test Topics

Why the other answers are wrong

  • Liquid — Liquid charged into a deep vacuum can flash and freeze the water in the tubes.
  • Nitrogen — Nitrogen is not part of charging and would have to be purged.
  • Oil — Oil is not charged ahead of refrigerant to protect the tubes.

Practice more of this

More EPA 608 Type III practice questions, or see every EPA 608 practice test.