Why must an idle low-pressure chiller usually be brought above atmospheric pressure before it is leak tested?
Leak detection · EPA 608 Type III. The correct answer, and the reasoning behind it.
Pressurizing low-pressure systems for leak tests, signs of leaks, inspections and reports.
The question
Why must an idle low-pressure chiller usually be brought above atmospheric pressure before it is leak tested?
- Leak detectors only work above 15 psig
- EPA requires every low-pressure leak test to be done at exactly 10 psig
- R-123 cannot be detected while it is a liquid
- Below atmosphere, leaks pull air in instead of pushing refrigerant outCorrect answer
Why “Below atmosphere, leaks pull air in instead of pushing refrigerant out” is correct
At room temperature an R-11 or R-123 chiller sits near or below atmospheric pressure. Any leak then draws air inward, so there is no refrigerant escaping for a detector or bubble solution to find. Raising the internal pressure slightly above atmosphere makes the leaks push refrigerant out where they can be located.
Source: EPA: Test Topics
Why the other answers are wrong
- Leak detectors only work above 15 psig — Detectors do not need 15 psig, and that pressure would be unsafe on a low-pressure chiller.
- EPA requires every low-pressure leak test to be done at exactly 10 psig — No rule sets a leak test pressure; 10 psig is a maximum, not a required value.
- R-123 cannot be detected while it is a liquid — The issue is the direction of flow through the leak, not the state of the refrigerant.
Practice more of this
More EPA 608 Type III practice questions, or see every EPA 608 practice test.