Which method may a technician use to bring an R-123 chiller up to 0 psig before a non-major repair?
Recovery requirements · EPA 608 Type III. The correct answer, and the reasoning behind it.
Evacuation levels for low-pressure appliances, and major versus non-major repairs.
The question
Which method may a technician use to bring an R-123 chiller up to 0 psig before a non-major repair?
- Controlled hot water or a built-in heating device such as PrevacCorrect answer
- Dry nitrogen from a regulated cylinder, with the nitrogen purged afterward
- Compressed shop air fed through the purge connection
- Carbon dioxide from a cylinder, purged afterward
Why “Controlled hot water or a built-in heating device such as Prevac” is correct
Low-pressure appliances whose refrigerant boils at or below 85 °F at standard atmospheric pressure, such as R-11 and R-123, must not be pressurized with methods that require later purging. Warming the refrigerant with controlled hot water or a built-in heating and pressurization device raises its own vapor pressure instead.
Source: 40 CFR 82.156(a)(1)(ii); EPA: Test Topics
Why the other answers are wrong
- Dry nitrogen from a regulated cylinder, with the nitrogen purged afterward — R-123 boils below 85 °F at atmospheric pressure, so methods such as nitrogen that need later purging are not allowed.
- Compressed shop air fed through the purge connection — Air is a noncondensable that would have to be purged out and would contaminate the refrigerant.
- Carbon dioxide from a cylinder, purged afterward — CO2 would also need to be purged out later, which the rule forbids for R-123.