Which group lists only refrigerants that 40 CFR 82.152 names as examples for low-pressure appliances?

Recovery requirements · EPA 608 Type III. The correct answer, and the reasoning behind it.

Evacuation levels for low-pressure appliances, and major versus non-major repairs.

The question

Which group lists only refrigerants that 40 CFR 82.152 names as examples for low-pressure appliances?

  • R-12, R-134a, R-500 and R-114
  • R-22, R-410A, R-407C and R-404A
  • R-11, R-123, R-113 and R-245faCorrect answer
  • R-13, R-23, R-503 and R-508B

Why “R-11, R-123, R-113 and R-245fa” is correct

The definition of a low-pressure appliance lists R-11, R-123, R-113 and R-245fa as examples. All four have saturation pressures below 45 psia at 104 °F, which is why they are found in centrifugal chillers that operate near or below atmospheric pressure.

Source: 40 CFR 82.152

Why the other answers are wrong

  • R-12, R-134a, R-500 and R-114 — These are higher-pressure refrigerants; none of them is a low-pressure example in the definition.
  • R-22, R-410A, R-407C and R-404A — These run at much higher pressures and are typical of Type II equipment.
  • R-13, R-23, R-503 and R-508B — These are the examples EPA gives for very high-pressure appliances.