What does this mean?

Recovery techniques · EPA 608 Type II. The correct answer, and the reasoning behind it.

Recovering liquid first, speeding recovery, and avoiding cross-contamination.

The question

A technician pulls a 200-pound R-22 system down to 10 inches of Hg vacuum, closes the valves, and five minutes later the gauge reads 2 psig. What does this mean?

  • The gauge needs recalibrating
  • Air has leaked into the system through the hose connections
  • Refrigerant is still in the liquid or the oilCorrect answer
  • The system is ready to open

Why “Refrigerant is still in the liquid or the oil” is correct

A pressure rise after recovery stops shows refrigerant is still boiling off, from leftover liquid or from the oil. The technician must resume recovery until the required level holds.

Source: EPA: Test Topics; 40 CFR 82.156(a)

Why the other answers are wrong

  • The gauge needs recalibrating — A rise like this is the expected sign of remaining refrigerant, not a gauge fault.
  • Air has leaked into the system through the hose connections — Air leaking in is not the usual reason for a quick climb above 0 psig.
  • The system is ready to open — The required level is no longer met, so the system cannot be opened.