Under the 40 CFR Part 84 rule in effect from January 1, 2026, what trigger leak rate applies?
Leak repair requirements · EPA 608 Type II. The correct answer, and the reasoning behind it.
Leak-rate thresholds, repair deadlines, extensions and records.
The question
A walk-in freezer at a restaurant holds 20 pounds of R-404A, an HFC. Under the 40 CFR Part 84 rule in effect from January 1, 2026, what trigger leak rate applies?
- 10 percent
- 30 percent
- 20 percentCorrect answer
- None; it is below 50 pounds
Why “20 percent” is correct
Part 84 leak repair covers appliances with 15 pounds or more of an HFC with a global warming potential above 53, such as R-404A. Restaurant refrigeration is commercial refrigeration under 40 CFR 84.102, which has a 20 percent trigger rate.
Source: 40 CFR 84.106(a); 40 CFR 84.106(c); 40 CFR 84.102
Why the other answers are wrong
- 10 percent — 10 percent is the comfort cooling rate.
- 30 percent — 30 percent is the industrial process refrigeration rate.
- None; it is below 50 pounds — The 50-pound threshold is for Part 82; Part 84 starts at 15 pounds.
Practice more of this
More EPA 608 Type II practice questions, or see every EPA 608 practice test.
Unofficial, not affiliated with the EPA or any EPA-approved certifying organization. Questions are original practice written from public EPA material, not real exam questions.