Under 40 CFR Part 82, above what annual leak rate must leaks be repaired?
Leak repair requirements · EPA 608 Type II. The correct answer, and the reasoning behind it.
Leak-rate thresholds, repair deadlines, extensions and records.
The question
An office building's comfort-cooling chiller holds 150 pounds of R-22. Under 40 CFR Part 82, above what annual leak rate must leaks be repaired?
- 10 percentCorrect answer
- 15 percent
- 20 percent
- 30 percent
Why “10 percent” is correct
Comfort cooling appliances, and any other appliance with 50 or more pounds that is not commercial or industrial process refrigeration, have a 10 percent trigger rate. Chillers used to cool occupied buildings are named as comfort cooling in the definition.
Source: 40 CFR 82.157(c); 40 CFR 82.152
Why the other answers are wrong
- 15 percent — No category has a 15 percent rate.
- 20 percent — 20 percent is the commercial refrigeration rate.
- 30 percent — 30 percent is the industrial process refrigeration rate.
Practice more of this
More EPA 608 Type II practice questions, or see every EPA 608 practice test.