A technician builds a homemade pump rig to recover refrigerant from refrigerators. Why can't it be used for the job?

Recovery requirements · EPA 608 Type I. The correct answer, and the reasoning behind it.

The small-appliance definition and the recovery levels required.

The question

A technician builds a homemade pump rig to recover refrigerant from refrigerators. Why can't it be used for the job?

  • Homemade rigs are allowed if they reach 90 percent
  • Homemade rigs are allowed on units under 2 pounds
  • Homemade rigs are allowed whenever the technician holds Universal
  • Recovery must use equipment certified under 40 CFR 82.158Correct answer

Why “Recovery must use equipment certified under 40 CFR 82.158” is correct

Section 82.156(b) requires recovery from small appliances using a recovery and/or recycling machine certified under 82.158. Only equipment made before November 15, 1993 can be treated as certified without lab testing, and only if it meets the performance level.

Source: 40 CFR 82.156(b); 40 CFR 82.158(e)

Why the other answers are wrong

  • Homemade rigs are allowed if they reach 90 percent — Equipment made after November 15, 1993 must be certified by an approved testing organization.
  • Homemade rigs are allowed on units under 2 pounds — There is no charge size below which uncertified equipment may be used.
  • Homemade rigs are allowed whenever the technician holds Universal — Certification of the technician does not replace certification of the equipment.

Practice more of this

More EPA 608 Type I practice questions, or see every EPA 608 practice test.

Unofficial, not affiliated with the EPA or any EPA-approved certifying organization. Questions are original practice written from public EPA material, not real exam questions.